ELK-M1XIN  
M1 16 Zone Input Expander
 
Adds 16 hardwired zones (EOL resistor supervised) to the M1 Gold or M1EZ8 Controls. Operates from 4-wire data bus. Up to 12 of these can be used, increasing total zones (inputs) to 208.

FEATURES:

  • 16 EOL Resistor Supervised Hardwire Zones

  • Operates on the 4-Wire Data Bus

  • DIP Switch Address Settings

  • Flash Memory for Firmware Updating

  • Plug-In Terminal Strips

  • Status and Diagnostic LED

  • On-Board EOL Bus Termination Jumper

  • Vertical Mounting using ELK-SWG Glides(included)

SPECIFICATIONS:

  • Inputs: Plug-In Terminals with Elevator Style Wire Clamps 
    and Screws

  • Operating Power Range: 
    9 to 14 VDC

  • Current Draw: 65 mA

  • Size: 6" x 3.25" x .75" H

View the ELK-M1XIN Installation Manual in Adobe Acrobat format (right-click to save document to your hard drive)

ELK-M1XOV  
M1 16 Output Expander, 
Flying Voltage Leads

Adds 16 voltage outputs to M1 Gold or M1EZ8 Controls. Provides 2 plug-in, 8-pin flying lead connectors for triggering low current devices (50 mA max. each such as: LEDs, relays, piezos, etc. Operates from 4-wire data bus. Up to 12 Output Expanders may be used for a total of 208 outputs. The voltage outputs can be converted to relays (8 or 16) using (1 or 2) M1RB Relay Board(s).

FEATURES:

  • 16 Voltage Outputs

  • Operates on the 4-Wire Data Bus

  • DIP Switch Address Settings

  • Flash Memory for Firmware Updating

  • Two (2) - Twelve (12) Conductor "Flying Lead" Wire Harnesses

  • Voltage Outputs may be converted to Relays using M1RB Relay Boards

  • Status LED with Diagnostic Display

  • Mounts in Enclosure using ELK-SWG Glides, SWP3 Structured Wire Plate, or Double Sided Foam Tape

SPECIFICATIONS:

  • Outputs: 12 VDC @ 50 mA each

  • Wire Harness Length: 12"

  • Operating Power Range: 9 to 14 VDC

  • Current Draw: 65 mA Nom., 330 mA Max.

  • Size: 6" x 3.25" x .75" H

 

View the ELK-M1XOV Installation Manual in Adobe Acrobat format (right-click to save document to your hard drive)

ELK-M1XOVR  
M1 16 Output Expander, 
8 Voltage & 8 Relays

Adds 16 outputs (8 voltage, 8 relays) to M1 Gold  or M1EZ8 Controls. Voltages can be used to trigger low current devices (50 mA max. each). Relays are SPDT rated for 7A @ 30 VDC, 10A @ 125 VAC. Operates from 4-wire data bus. Up to 12 output expanders may be used for a total of 208 outputs. Option: Convert 8 voltage outputs to relays using M1RB Relay Board.

FEATURES:

  • 8 Voltage Outputs

  • 8 Single-Pole, Double-Pole Relay Outputs

  • Operates on the 4-Wire Data Bus

  • DIP Switch Address Settings

  • Flash Memory for Firmware Updating

  • One (1) - Twelve (12) Conductor "Flying Lead" Wire Harness

  • Voltage Outputs may be converted to Relays using M1RB Relay Boards

  • Status LED with Diagnostic Display

  • Mounts in Enclosure using ELK-SWG Glides, SWP or SWP3 Structured Wire Plates, or Double Sided Foam Tape

SPECIFICATIONS:
  • Voltage Outputs: 12 VDC @ 50 mA each

  • Relay Outputs: 
    SPDT rated for 7 Amps @ 28VDC, 
    10 Amps @ 125 VDC

  • Wire Harness Length: 12"

  • Operating Power Range: 9 to 14 VDC

  • Current Draw: 65 mA Nom., 330 mA Max.

  • Size: 6" x 3.25" x .75" H

View the ELK-M1XOVR Installation Manual in Adobe Acrobat format (right-click to save document to your hard drive)

ELK-M1RB  
M1 Relay Board, 
Plug-in (8 form ”C” relays)

May be plugged directly into an M1G, M1EZ8, M1XOV, or M1XOVR to convert the voltage outputs into SPDT relays rated for 7A @ 30 VDC, 10A @ 125 VAC.

FEATURES:

  • 8 Form "C" Relays, SPDT Dry Contact

  • Heavy Duty Contact Rating

  • Low Current Draw.

  • Great For General Purpose Switching.

  • Plug-in "Removable" Terminal Blocks

  • LED Status Indicators on all 8 Relays

  • Twelve (12) Conductor Plug-in Wire Harness

  • Mounts in Enclosure using ELK-SWG Glides

SPECIFICATIONS:
  • Diode Protection Across Relay Coil.

  • Contact Ratings: 
    7 Amps @ 28 VDC, 10 Amps @ 125 VAC

  • Wire Harness Length: 24"

  • Operating Voltage: 12 Volts DC Nominal

  • Current Draw: 0 mA idle, 250 mA Max.

  • Size: 6" x 3.25" x .75" H

View the ELK-M1RB Installation Manual in Adobe Acrobat format (right-click to save document to your hard drive)