Notification of Critical Temperatures


In the food service industry, some very costly inventory is stored in freezers and coolers.  The same is true for grocery stores, home owners, etc. If freezers or coolers fail, it can be expensive and time consuming.  For every moment the failure goes unnoticed, the problems become increasingly amplified.  The M1 Cross Platform Control can monitor freezers, coolers, boilers, wine cellars, aquariums, ponds, second homes, warehouses, storage tanks, livestock barns, etc. and contact you if the temperature is not in an acceptable range.   


In this example, a cooler is being monitored every 30 minutes.  The desired cooler temperature is 42 degrees so, if the temperature rises above 45 degrees F, the M1 will dial the “Maintenance’ number and announce “Temperature Alert, Check Cooling Unit One”.  The second rule produces the same effect if the temperature falls below 40 degrees F.
 

(Note: Message can be customized using the 500+ word/phrase vocabulary or the 10 custom recordable words/phrases) 

WHENEVER EVERY 30 MINS
     AND Zone 016 (Zn 16) ACTUAL TEMPERATURE IS GREATER THAN 45 DEG. F. (7 DEG. C.)
            THEN DIAL Maintenance (5551234) AND ANNOUNCE Miscellaneous 4 (vm242) 

WHENEVER EVERY 30 MINS
     AND Zone 016 (Zn 16) ACTUAL TEMPERATURE IS LESS THAN 40 DEG. F. (4 DEG. C.)
            THEN DIAL Maintenance (5551234) AND ANNOUNCE Miscellaneous 4 (vm242) 

To insure that a person (not an answering machine) receives the message, it may be desired to contact more than one number.  To do this, just add another then statement to the rule. 

WHENEVER EVERY 30 MINS
     AND Zone 016 (Zn 16) ACTUAL TEMPERATURE IS GREATER THAN 45 DEG. F. (7 DEG. C.)
            THEN DIAL Maintenance (5551234) AND ANNOUNCE Miscellaneous 4 (vm242)
            THEN DIAL Manager (5552345) AND ANNOUNCE Miscellaneous 4 (vm242)  

Each primary number can have one backup number.  This number will be dialed if the primary number cannot be reached.  This option is available in the “Telephones” screen for each number.

 

The customer may wish to receive an email in addition to or in lieu of a phone call.  This is possible using the ELK-M1XEP email feature.  Once the email feature has been properly configured, the rule can be edited as shown below.

 

WHENEVER EVERY 30 MINS
     AND Zone 016 (Zn 16) ACTUAL TEMPERATURE IS GREATER THAN 45 DEG. F. (7 DEG. C.)
            THEN DIAL Maintenance (5551234) AND ANNOUNCE Miscellaneous 4 (vm242)

            THEN SEND EMAIL MESSAGE 1 TO manager@bizwebaddress.com


Welcome to our blog, the Security & Automation Connection!


Learn more about security, home automation, business solutions, energy management, access control, and many other solutions available though ELK's M1 Cross Platform Controls. Our goal is to make this blog a great resource for getting new ideas on how to take advantage of the powerful integration and programming capabilities of the M1. We will also provide tech tips and how-to's on a variety of applications to get you well on your way to securing and simplifying life!